The following requirements must be met, in the order given, before circuits or equipment are reenergized, even temporarily.

  1. A qualified person must conduct tests and visual inspections, as necessary, to verify that all tools, electrical jumpers, shorts, grounds, and other such devices have been removed, so that the circuits and equipment can be safely energized.
  2. Employees exposed to the hazards associated with reenergizing the circuit or equipment must be warned to stay clear of circuits and equipment.
  3. Each lock and tag must be removed by the employee who applied it or by someone under his or her direct supervision. However, if this employee is absent from the workplace, then the lock or tag may be removed by a qualified person designated to perform this task provided that:
    • The employer ensures that the employee who applied the lock or tag is not available at the workplace, and
    • The employer ensures that the employee is aware that the lock or tag has been removed before he or she resumes work at that workplace.
  4. There must be a visual determination that all employees are clear of the circuits and equipment.

To learn more about Construction Lockout/Tagout visit our Construction Lockout/Tagout Online Training web page.

THE BEST ONLINE TRAINING EXPERIENCE POSSIBLE

Fast

Your time is valuable. We've designed our site to be as fast as possible.

Easy to use

You'll never get lost or confused with us.

Immediate Access

There's no waiting period. Begin the course as soon as you sign up.

Anywhere Anytime

Internet connection and a computer, tablet, or smartphone.

Up to date

We update our courses as soon as new regulations come out.