Outside Conductors, 600 Volts or Less
Certain requirements apply to branch-circuit, feeder, and service conductors run outdoors as open conductors that are rated 600 volts nominal or less.
Conductors on poles must have a separation of no less than one foot when not placed on racks or brackets. Conductors supported on poles must provide a horizontal climbing space no less than the following:
- Power conductors below communication conductors: 30 inches
- Power conductors alone or above communication conductors: 24 inches for 300 volts or less; 30 inches for more than 300 volts
- Communication conductors below power conductors: Same as power conductors
- Communications conductors alone: No requirement